model |
DR-75-12 |
DR-75-24 |
HDR-75-48 |
|
output |
Dc output voltage |
12V |
24V |
48V |
Output voltage tolerance |
±2% |
±1% |
±1% |
|
Rated output current |
6.3A |
3.2A |
1.6A |
|
Output current range |
0-6.3A |
0-3.2A |
0-1.6A |
|
Output power |
76W |
76.8W |
76.8W |
|
Ripple and the noise |
100mVp-p |
150mVp-p |
240mVp-p |
|
Dc voltage adjustable scope |
17% |
17% |
10% |
|
Start, rise time |
1000ms,60ms/230VAC Loaded with 1800ms,60ms/115VAC Loaded with |
|||
Keep time |
60ms/230VAC12ms/115VAC Loaded with |
|||
input |
Input voltage range |
85~264 VAC choose 47~63 Hz;120~370VDC |
||
Exchange input current |
1.6 A/115 V 0.96A/ 230 V |
|||
efficiency |
76% |
80% |
81% |
|
Impulse current |
Cold start current 20A/115V 40A/230V |
|||
Leakage current |
<1mA/240VAC |
|||
Protection characteristics |
Overload protection |
105%~150% |
||
Protection way: constant current limiting automatic recovery | ||||
Overvoltage protection |
120%~140% |
|||
Protection way: hiccups, auto recovery mode | ||||
High temperature protection |
TSW1≥85ºC±5ºC, |
|||
Protection way: cut output, temperature down automatically restored | ||||
environment |
Working temperature, humidity |
-10ºC~+60ºC;20%~90 %RH |
||
Keep temperature, humidity |
-20ºC~+85ºC;10%~95 %RH |
|||
Vibrate resistance |
10 ~ 500 Hz ac, 2 G 10 min. / 1 cycle time, 60 minutes, the axis |
|||
security |
Compression sex |
3: KVAC between input and output and input and output KVAC: 1.5 to 0.5: KVAC |
||
Insulation resistance |
Between the input and output, the input and output, and ground: 100 M / 500 VDC Ohms |
|||
Complies with the standards |
Safety standards |
UL508,TUV EN60950-1 |
||
EMC standard |
EN55011,EN55022,EN61000-3-2,-3,EN61000-4-2,3,4,5,6,8,11,ENV50204,EN55024,EN61000-6-2 |
|||
other |
weight |
0.6Kg |
||
packaging |
20pcs/13Kg/1.1CUFT |
|||
note |
1. All the parameters in has not specified, all is in 230 VAC voltage input, rated load and 25 ºC conditions measuring income value. 2. Ripple and noise voltage is in 20 MHz bandwidth oscilloscope take 12 inches twisted pair end with 0.1 mu and 47 u when capacitance measurement. 3. Tolerance is voltage setting error, the voltage adjustment rate and adjust the sum total of the current rate. 4. The power to consider as a device installed in final equipment, this equipment must be to make sure it's EMC index. |